[Calculation of Heat Exchanger]Calculation Formula of Heat Exchanger and Surface Calculation Method of Heat Exchanger

[Heat Exchanger Calculation] Heat Exchanger Calculation Formula Heat Exchanger Heat and Surface Calculation Method

I. Heat Calculation

1, General

Q=Wh(Hh, 1-Hh, 2)=Wc(Hc, 2-Hc, 1)

where:

Q is the heat load of the heat exchanger, kj/h or kw;

W is the mass flow of the fluid, kg/ h;

H is the enthalpy of fluid per unit mass, kj/kg;

Subscripts c and h represent cold fluid and hot fluid, respectively, and subscripts 1 and 2 represent heat transfer, respectively import and export of appliances.

2, no phase change

Q=Whcp, h(T1-T2)=Wccp, c(t2- t1)

where:

cp is the average constant pressure specific heat capacity of the fluid, kj/(kg.℃);

T is the temperature of the hot fluid, ℃ ;

T is the temperature of the cold fluid, °C.

Second, area calculation

1, total heat transfer coefficientK

The K value in the shell and tube heat exchanger is as follows:

Note:

1w=1J/ s=3.6kj/h=0.86kcal/h

1kcal=4.18kj

2, temperature difference

(1) Counterflow

Hot fluid temperature T: T1→T2

Cold fluid temperature t: t2←t1

Temperature difference △t: △t1 →△t2

△tm=(△t2-△t1)/㏑(△t2/△t1)

(2) Parallel flow

Thermal fluid Temperature T: T1→T2

Cold fluid temperature t: t1→t2

Temperature difference △t: △t2→△t1

△tm=(△t2 -△t1)/㏑(△t2/△t1)

3, area calculation

S=Q/( K.△tm)

III. Calculation of the area of shell and tube heat exchanger

S=3.14ndL

Among them, S is the heat transfer area m2, n is the number of tubes in the tube bundle, d is the diameter of the tube, m; L is the length of the tube, m.

Four. Precautions

Condensing section: latent heat (calculated according to the heat of vaporization)

Cooling section: sensible heat (based on specific heat capacity calculation)